Potential Transformer

ViewView
  1. voltage Transformers

    SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS OF 11KV PT S. No Particular Detail 1. Type outdoor type 2. No of phase 3 3. Ratio of PT 11KV/110 4. Class 0.5 5. VA Burden 50 VA 6. Earthed Solidly neutral earthed 7. Nominal system voltage 11KV 8. Highest system voltage 12 KV 9. Insulation level 12/28/75KV(Peak)10. Confirming to ISS 3156/92 11. Application Metering 12. Rated voltage factor 1.2 continuous & 1.5 for 30 Sec 13. Rated freq. 50 Hz.14. Rated continuous thermal current temperature rise over ambient 50 Deg. C.
    Send Inquiry
  2. Drawout Potential Transformer

    SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS OF 11KV PT S. No Particular Detail 1. Type Epoxy resin cast, Indoor type 2. No of phase 3 3. Ratio of PT 11KV/110 4. Class 0.5 5. VA Burden 50 VA 6. Earthed Solidly neutral earthed 7. Nominal system voltage 11KV 8. Highest system voltage 12 KV 9. Insulation level 12/28/75KV(Peak)10. Confirming to ISS 3156/92 11. Application Metering 12. Rated voltage factor 1.2 continuous & 1.5 for 30 Sec 13. Rated freq. 50 Hz.14. Rated continuous thermal current temperature rise over ambient 50 Deg. C.
    Send Inquiry